Navigation

AJ110 supplied to a pharmaceutical company based in Craigavon.

The AJ110 powered by a Perkins engine has been supplied with a sound attenuated canopy to provide sound reduction due to its outdoor application. The bunded base comes complete with bund leakage alarm which is wired back to the InSight 3250 control panel.

A fuel transfer system has been set up to allow 72 hours running, connecting the generating set to an external 1800L bunded plastic tank. The system is complete with a watchman level monitoring system installed with double skinned pipework.

Larger terminals on the genset circuit breaker have been supplied to allow the connection of 2 x 95mm² cables per phase on the load side due to long cable run between the generating set and the lab.

The InSight 3250 control panel has been supplied with volt free contacts to allow monitoring of parameters by BMS which is connected to an alarm panel located in the lab. These alarms includes genset running, low fuel level, genset in test mode and switchboard auto changeover.