This LV panel houses a DSE7420 control panel, 400A ATS changeover switch and 2 x 400A circuit breakers - one for the genset and one for testing with a loadbank (shunt trip on this CB to ensure the genset is in AMF mode at all times). The DSE7420 panel controls the generator and the ATS panel.